"We want to know when a valve lifts, and which one is lifted." Singapore Refining Co.'s Jian Ting Kwan, on the company's use of Emerson wireless acoustic sensors to track pressure relief valve behavior.
By automatically monitoring valves, it should be possible to quantify and reduce flaring and vent losses, effectively inspect valves and schedule overhauls, and correlate passing to process conditions to improve operations.
"We want to know when a valve lifts, and which one is lifted," Kwan said. "When a valve seats back, it often doesn't seat back completely, and we want to know that, too."
Mission: Smart relief valves
The plant defined a mission to turn ordinary relief valves into smart relief valves by installing leak detection instruments. "A wireless acoustic transmitter detects ultrasonic emissions due to passage of liquid or gas, with a secondary indication by temperature," Kwan said. "There's no need to upgrade the DCS or historian, and no special software required."
The acoustic instruments are easy to install, and transmit data to the wireless receiver, which routes it to the DCS, where operators can see the overpressure release as an indication of process problems. It also feeds the historian, where Energy and Loss Control can use it to monitor losses, Maintenance can use it to plan and prioritize repairs, and EH&S can use it for reporting.
Phase 1 demonstrated value
An Emerson acoustic leak detector trial was carried out from January 2013 to May 2014. The trial involved real-time monitoring of both steam traps and the flare system. The installation includes a gateway, management software and 50 wireless transmitters spread across the site: three on relief valves, two on control valves, 29 on stream traps and 16 as repeaters for the WirelessHART mesh network.
The results on steam traps were very encouraging. Verified against a portable tester, 97% gave the same result. Seven of the 29 team traps were found faulty instantly on installation, with six leaking and one trapping condensate.
Phase 1 showed that the transmitters could detect passing and leaks, but high background noise affected the accuracy of results, especially on relief valves.
Phase 2 promises payback
The refinery is now planning to install 224 additional transmitters, including 184 on relief valves. This phase also includes three flowmeters to pinpoint areas of high flare flow. Kwan calculates 31 kg/hr potential flare reduction, or 30% of the facility's historical releases. He estimates the resulting savings at US$114,700 per year, plus increased maintenance efficiencies.
Using the transmitters' temperature indication will help overcome noise problems, and the latest version of the 708 has the ability to suppress background noise as well.
"This application uses Modbus [to connect the wireless gateways with the DCS], but we can use HART-IP or other network protocols," said Jonas Berge, director, applied technology, Emerson Process Management. The same wireless system is being used for many other things in the plant, such as monitoring vibration, corrosion, inventory and materials movements.
Wireless networks and acoustic transmitters have broad applications in many plants for steam trap and other equipment monitoring, as well as for relief and pressure control valves, Berge said. "All plants that use relief valves have these challenges—to cut flaring and prevent losses by pinpointing which valves are lifting or leaking."