Table 1: Switching contact configurations*
Now, coming to your specific question concerning contact arrangements, the number, type and arrangement of contacts and circuits determines the switching capacity. Table 1 lists the related terminology. The usual abbreviations used include:
Normally open (NO): The circuit is open (current does not flow) when the contacts are not actuated. Moving them to the other extreme position completes (closes) the circuit.
Normally closed (NC): The circuit is complete when the switch is not operated. Moving the contacts opens the circuits, interrupting current flow.
Number of poles (P): The number of conductors in which current will be simultaneously started or interrupted by one operation of the switch.
Number of throws (T): The number of positions at which the contacts will provide complete circuits. Since contacts usually have only two extreme positions, switches are either single-throw or double-throw.
As shown in Figure 1, Form C contacts are composed of a normally-closed contact pair and a normally-open contact pair that are operated by the same actuator device. Instead of the term Form C, industrial users often use the alternate name SPDP (single-pole, double-throw) for this configuration. There is a common electrical connection between a contact of each pair that results in only three connection terminals. These terminals are usually labelled as normally open, common, and normally closed (NO-C-NC). These contacts are quite frequently found in electrical switches and relays as their common contact element provides a mechanically economical method of providing a higher contact count.
Béla Lipták
[email protected]
A: We always used Form C relays for all applications, and used both contacts for the logic. The result was that a 1-0 or 0-1 were the only acceptable readings: 1-1 or 0-0 always indicated a fault (contact or wiring). We didn’t have a standard for a difference between alarm and status. I realize that this makes logic diagramming and programming a little more difficult, but reliability is far more important.
Dick Caro , CEO, CMC Associates
ISA Life Fellow
[email protected]
A: NO, NC refer to the relay being de-energized or powered off. So, to have “open to alarm” condition, the NO contact would be used for this. A loss of power would look like the alarm condition. A good reference is https://en.wikipedia.org/wiki/Electrical_contacts.
Bruce B. Burton
R&D program manager
[email protected]
A: NO and NC are the fundamental blocks of understanding any logic, be it soft or hardware. Normal condition is defined as energized condition and when plant/equipment/machine is running in normal condition, logic is true.
NC means normally-closed contact. NO means normally-open contact. When the relay coil is de-energized, NC contact becomes open, and NO contact closes.
For alert and emergency shutdown (ESD) logic, a break-to-alarm philosophy is employed so that during an emergency, NC contact will become open and trip/provide alarm. Normally, high (H) and high high (HH) switches (level, pressure, etc) are designed as NC. Low (L) and low low (LL) contacts are defined as NO. You can call me at +971504874184 for a detailed discussion.
Debasis Guha
Deputy manager C&I, Petrofac
[email protected]
A: This is very good observation, because this is not a well understood issue in many industrial and medical applications. Plus, there are unique issues when working with fiber optic sensor/switch systems. Fiber optic sensor systems consist of the sensor, fiber optic link and controller (which incorporates a relay providing dry contacts). Sensors typically use two fibers so the sensor, link and controller form a continuous optical loop when connected. The two states are referred to as MonitoringState and EmergencyState. The relay contacts (NO or NC) are used as is appropriate to the application. A microswitch plunger is mechanically triggered to the opposite state (moves an internal mirror so that the optical circuit is broken).
In the normal monitoring state, the optical circuit is ON and continuity exists between the E-stop/switch and corresponding controller. With the E-stop in reset position, if the microswitch requires plunger DOWN, then NO order option is chosen. If the microswitch requires plunger UP, then NC order option is chosen.
The emergency state is triggered by power loss, fiber optic link damaged, fiber optic disconnection or E-stop activated (plunger down breaks the internal optical circuit).
Dennis Horwitz
Micronor Inc.
[email protected]